A light meter tells you whether light arrives. An OTDR tells you where it was lost — and that difference is the whole point. The trace is a map of the span: distance along the bottom, loss down the side, and every step down is an event at a known location. Read it event by event, match each event to something real on the span, and you can tell a bad splice from a dirty connector from a bend without opening a single tray. Read it as a pass/fail verdict and it will mislead you at least as often as it helps.
The OTDR fires pulses down the fiber and measures the light scattered back. The steady downward slope is the fiber's own attenuation (about 0.2 dB/km at 1550 nm on single-mode, about 0.35 dB/km at 1310 nm). Anything steeper than that slope is an event. Two things matter about each event: how much loss it shows, and whether it carries a reflective spike. The spike is the fingerprint — connectors reflect, splices (good ones) do not.
| Event signature | What it usually is | Typical loss (single-mode) |
|---|---|---|
| Small step, no spike | Fusion splice | 0.05–0.1 dB |
| Step with a sharp spike | Connector or mechanical splice | 0.2–0.5 dB |
| Step, no spike, worse at 1550 nm than 1310 nm | Bend (pinch, tight radius, crushed cable) | Varies — compare wavelengths |
| Step upward ("gainer") | Splice between different fiber types, seen from one direction only | Apparent gain, not real |
| Large final drop | End of fiber (or a break) | End of trace |
Those loss figures are rules of thumb for judging whether an event is worth chasing, not acceptance limits for your plant — your site's spec is the limit that matters. A 0.4 dB connector is unremarkable; a 0.4 dB fusion splice is worth re-doing. The signature tells you which one you are looking at.
Chasing ghosts. A ghost event sits at a distance equal to the sum of two real reflections, often beyond the end of the fiber. It looks exactly like a fault and there is nothing at that location to fix. The other-direction shot is the only reliable test — do it before opening any tray.
Reading a gainer as a repair. A splice that reads as a gain from one direction has not improved the fiber; it joins two fiber types with different backscatter levels. Average both directions for the true loss, and write both numbers in the ticket, or the next tech will read the single-direction gain and conclude the splice is "better than perfect."
Testing at the wrong wavelength. A span qualified at 1310 nm can fail at 1550 nm (bend sensitivity) and vice versa. Test at the wavelength the optics actually use, and say which wavelength you used — a trace without its wavelength is unverifiable.
A trace summary that nobody can re-check is barely better than no trace. The minimum useful note:
Span: SW-11 ↔ SW-14 via ODF-C (expected length 3.4 km). OTDR 1550 nm from ODF-C, launch cable fitted. Splice tray 1.24 km: 0.08 dB (normal). Bulkhead 2.01 km: 0.35 dB (connector, within spec). End of fiber 3.42 km (matches record — span complete). Total loss 1.9 dB. Trace file attached: otdr-sw11-sw14-1550.pdf. No fault found on this span; fault lies elsewhere.
The shape to copy: span and expected length, wavelength and direction, each event with distance and loss, total loss, the trace file itself, and the conclusion the trace supports. "OTDR shows no fault" without wavelength, direction, and distances is an assertion; with them, it is evidence the next tech can stand behind.
See RackReady Free sample Fiber no-link checklist
Support: support@hasherventures.com
Free tool: turn your trace findings into a structured ticket note with the RackReady Ticket Builder.