Server Won't Power On: Troubleshooting Checklist

No power is a physical-layer problem until you prove otherwise. Do not start by reseating random parts — work this order, document each result, and you will either fix it or hand the engineer a case that needs no follow-up questions.

The fixed order

  1. Safety first. Burning smell, scorch marks, or a tripped smell near the rack: stop, keep hands off, escalate to your lead/facilities.
  2. Read the PSU LEDs. Dark PSU = no feed reaching it. Amber/blinking = PSU fault. Note which PSU (1/2) and the exact state — this single observation splits the problem in half.
  3. Verify the PDU feed. Is the outlet live? Check the PDU display, a neighbor on the same feed, and whether feed A or B is down.
  4. Reseat power cables at both ends. PSU end and PDU end. If nothing changes, swap in a known-good cable.
  5. Check front panel and management. Any standby power signs? Does the management controller (iDRAC/iLO/IPMI) respond? Standby present but no power-on points inside the chassis; nothing at all points at the feed.
  6. Ask what changed. PDU maintenance, a rack move, a neighbor's RMA. Sudden no-power after nearby work is rarely a coincidence.
  7. Swap the PSU if authorized. Known-good, same rating. Fault follows the PSU → PSU. Fault stays → feed or chassis.
  8. Document and escalate. PSU LED states, feed verified how, cable/PSU swap results, and your specific ask.

Two traps