Fiber Transceiver DOM Readings: Tx Power, Rx Power, Temperature, and When to Escalate

The fastest fiber fault to fix is the one you never open. Before you pull a patch cord, open a panel, or swap an optic, the optic itself will tell you what is wrong — if you ask it. Every modern SFP and QSFP reports DOM values (Digital Optical Monitoring, also called DDM): transmitted power, received power, temperature, supply voltage, and laser bias current. Reading them takes a minute from the switch CLI, costs nothing, and answers the first question on any fiber fault: is the problem the optic, or the span behind it? A tech who swaps the optic first and reads DOM second has already wasted the part and the maintenance window.

The five DOM values, and what each one means

ValueWhat it isHealthy looks likeOut of range means
Tx power (dBm)How much light this optic is sendingInside the range printed on the optic's datasheet (for example -7 to -1 dBm on a typical 10G short-reach optic)Laser failing or degraded — this optic is the suspect, plan a swap
Rx power (dBm)How much light is arriving at this opticSeveral dB above the receiver sensitivity on the datasheet (typically about -11 dBm short-reach, about -14 dBm long-reach)Loss somewhere in the span — or the far-end optic is sending weak light; check the far end before touching the fiber
Temperature (°C)The optic's own temperatureWithin the rated range — 0 to 70 °C for a commercial opticAbove range: blocked airflow, a hot slot, or a failing optic cooking itself
Supply voltage (V)Power the slot is feeding the optic3.3 V, within ±5% (3.135 to 3.465 V)Out of range: the slot or the switch power, not the optic — reseat, try another slot, escalate to the platform team
Tx bias current (mA)How hard the laser is being drivenStable over time and inside the datasheet rangeClimbing over weeks while Tx power holds steady: the laser is compensating for age and is near end of life — replace before it fails, not after

How to read DOM on your gear

The command depends on the platform, but the values are the same everywhere. On a Cisco switch: show interfaces transceiver detail. On Arista: show interfaces transceiver dom. On Juniper: show interfaces diagnostics optics. On a Linux server NIC: ethtool -m eth0. Read both ends of the link — a one-ended DOM read is half the evidence, because a low Rx on your end is either your span or the far end's Tx, and only the far end's numbers tell you which. If the optic reports no DOM at all, it is either a very old optic or a third-party optic with DOM disabled; that itself is worth one line in the ticket, because it means the next fault on that link will have no self-reported evidence.

The decision flow: optic, span, or something else

  1. Rx low, far-end Tx normal → the span. Light leaves the far end fine and arrives weak. Clean and inspect the connectors (see the connector cleaning guide), then compare the measured loss against the loss budget. Do not swap the optic.
  2. Tx low on this end → this optic. The laser is not sending enough light. Swap the optic, re-read DOM on the new one, and record both readings so the ticket shows the before and after.
  3. Rx low and far-end Tx low → the far-end optic. The far laser is the fault. Escalate with both ends' numbers attached — the far-end team can verify from the ticket without re-measuring.
  4. Bias current climbing, Tx still in spec → a dying optic, not a dead one. This is the catch that saves an outage: a laser near end of life drives its bias up to hold Tx power steady, so the link looks fine until it suddenly is not. Record the bias trend, raise a planned replacement, and do not wait for the alarm.
  5. Temperature high → airflow, not the optic. Check the blanking panels, the fan, and what is stacked above the switch before blaming the transceiver. A hot optic in a hot slot will fail again after the swap.
  6. Voltage out of range → the slot. Reseat the optic, try a known-good slot, and if the voltage follows the slot, the switch or its power feed is the fault — escalate to the platform team, not the optics spares shelf.

Alarms vs warnings: which threshold matters

DOM carries two sets of thresholds per value: a warning and an alarm. A warning means the value is drifting toward the edge of spec — worth a ticket line and a planned look. An alarm means it is out of spec now — the link is degraded or about to drop, and the ticket should say so plainly. The common mistake is treating a warning as noise and only acting on the alarm: by the time Rx power alarms, the link has already been marginal for days, and every ticket written in that window says "intermittent" because nobody read the warning. When you open a fiber ticket, copy the DOM values into it even when they are healthy — a healthy baseline is what makes the next fault diagnosable in minutes instead of hours.

Recording DOM in the ticket

A DOM reading without its thresholds is just numbers; with them, it is a verdict. The minimum useful line records both ends, all five values, and the call:

SW-04 Gi1/0/12 ↔ SRV-22 eth0, 10G-SR, 85 m OM4.
This end DOM: Tx -3.2 dBm, Rx -6.8 dBm, temp 41 C,
Vcc 3.31 V, bias 6.8 mA.
Far end DOM: Tx -3.0 dBm, Rx -7.1 dBm.
Rx 4.3 dB above -11.1 dBm sensitivity → optics healthy;
fault is in the span, not the optic.

The shape to copy: link, optic type, both ends' DOM, Rx margin above sensitivity, and the verdict — optic, span, airflow, or slot. Seven fields, and the next person on the ticket can see in one line whether the optic was ever the suspect, without re-reading anything.

Fiber series: fiber no-link checklist · fiber light level readings · fiber splice ticket note · bad optic escalation · connector inspection and cleaning · TX-RX polarity check · single-mode / multimode mismatch · how to read an OTDR trace · fiber loss budget · OTDR dead zone and launch cable · light source and power meter test · OTDR settings that change the answer · DAC vs AOC vs optic · fiber slack management · fusion splice loss · single-mode vs multimode selection · fiber end-face inspection · fiber bend radius · fiber connector types.